— Commercial Water Mist
Pump Unit
— High Pressure
Applications
As a partner of Ultra Fog, we have full access to the complete range of pump sets they manufacture which are approved to cover a wide range of commercial and industrial uses.
Ultra Fog are a world leader in the manufacture of water mist systems, designing pump sets, nozzles and supply the full system including all pipework and fittings.
Our range of commercial water mist pump units are suitable for OH 1, OH 2, OH 3, OH 4 + FM 5560 hazards.
OH 1 - OH 2 - OH 3 - OH4 + FM5560 applications.
Master Pump Station
Outlet pressure: 100 – 140 bar.
Flow range: 94 – 150 litres/min/high pressure pump.
Power consumption: 22 – 30kw/high pressure pump.
Voltage supply: 3 x 400 VAC 50Hz (3 x440 VAC 60 Hz).
Control system with PLC and output/input for section valves, fire alarm system, power supply for feeder pumps etc.
External connections for alarm and control cabinets and operating panels through serial or TCP/IP communication.
OH 1 - OH 2 - OH 3 - OH4 + FM5560 applications.
Micro Pump Station
Outlet pressure: 100 – 150 bar.
Flow at 1500 rpm: 48 litres/min/pump.
Flow at 2200 rpm (optional): 75 litres/min/pump (frequency controlled).
Power consumption: 11 to 16 kw/pump/standard 50Hz.
Voltage Supply: 3 x 400 VAC 50Hz (3 x 440 VAC 60Hz).
Control system with PLC and output/input for section valves, fire alarm system, feeder pumps etc.
OH 1 - OH 2 - OH 3 - OH4 + FM5560 applications.
p35 Pump Station
Outlet pressure: 100 – 130 bar.
Inlet water ¬ow: 56 litres/min at 2 bar.
Flow: 35 – 50 litres/min.
Power consumption: 11kw.
Voltage supply: 3 x 400 VAC 50Hz (3 x 220 VAC 50Hz).
* For inlet water pressure between 0.7 – 2 bar an extra strainer shall be installed with 25 micron litre prior to pump inlet.